Product detail

ZGR SOLAR STR 100 /120
Three-phase String Inverters

ZGR SOLAR STR 100 /120

The ZGR SOLAR STR100 /120 offer high energy performance in a compact design, ideal for small-medium solar power plants.

Request information

Characteristics

The ZGR SOLAR STR 100 /120 string inverters are easy-to-use devices that have been designed to meet the needs of all grid-connected solar power plants without need for the use of transformers.

In an effort to improve the performance of solar power plants, these inverters offer high energy performance of over 98%. The ZGR SOLAR STR 100 /120 inverters are equipped with LED indicators, to facilitate the user to manage the inverter.

This range of string inverters offers a voltage range DC input, at full load, between 550 to 850 Vdc; and a rating of protection IP 66.

TECHNICAL SHEET
  • Multiple Maximum Power Point Trackers (MPPT)
  • High energy efficiency greater than 98%
  • Very low harmonic distortion, THD <3%
  • Direct connection to grid or to step-up transformer
  • Parallel connection without limitation
  • Equipment monitoring via LED and Bluetooth connection via mobile device
  • Anti-islanding protection with automatic disconnection
  • Protection against: Reverse polarization, short circuits, overvoltage, insulation faults
  • Compact design for easy installation

Technical Details

TECHNICAL SPECIFICATIONS
Model ZGR SOLAR STR100 ZGR SOLAR STR120
INPUT [DC]
Max. PV voltage 1100 V
MPPT range 550 - 850 Vdc
Nominal input voltage 620 V
DC starting voltage 200 V
MPPT number 10
Strings per MPPT 2
Max . Current per MPPT 26 A
Max. Short-circuit current per MPPT 35 A
Max. DC Current 35 A
Max. Current DC 260 A
OUTPUT [AC]
Nominal AC output power 100 kW @30 ºC 100 kW @40 ºC 100 kW @50 ºC 120 kW @30 ºC 110 kW @40 ºC 100 kW @50 ºC
Max. AC apparent power 100 kVA 120 kVA
Max. AC output power 100 kW 120 kW
Nominal AC Voltage 400 Vac, 320 - 480 V
AC Conection 3 W + N + PE
AC frequency range 50 / 60 Hz (± 5 Hz) (adjustable)
Nominal Output current 144,5 A 173,9 A
Max. Output current 147 A 176,4 A
Power factor range 0,8 captative - 0,8 inductive
THDi < 3%
EFFICIENCY
Ef!ciency (max) 99 %
European Efficiency 98,6 %
PROTECTIONS
Protections DC switch, Anti-islanding Protectión, Protection; Reverse Polarity DC Connection, String fault detection, Overvoltage DC/AC, Insulation Failure, Overcurrent Protection, AC short circuit.
ENVIRONMENTAL AND MECHANICAL CHARACTERISTICS
Topology Transformerless
Input terminal Amphenol
Cooling Method Forced air cooling (Fan)
Operating Temperature Range -25°C - 60°C (>40°C derating)
IP class IP66
Protection Degree Clase I
Noise emissions < 4000 m without derating
Pollution Degree PD3
Relative Humidity 0 - 100% (non-condesing)
Dimensions (Height x Width x Length) 1055 x 700 x 336 mm
Weight 96 Kgs
COMMUNICATIONS
Communications RS485
REGULATIONS
Certi!cacions and standards EN 62109-1: 2011 & EN 62109-2:2013; EN 61000-6-2 & EN 61000-6-4; VDE 0126-1-1; RD 244/2019 & UNE 217001:2020 ; EN206007 & UNE 217002:2020

Operations Manual

Hybrid, robust and reliable solutions

REQUEST FURTHER INFORMATION

If you want to know if you can purchase a product from the Zigor catalogue, you have questions on the operation and/or composition or simply want to know more about the Zigor products, leave your details and we will contact you. Furthermore, if you wish, you can download the complete catalogue by clicking on the button below.

DOWNLOAD 2024 CATALOGUE

    PRODUCT INFORMATION

    Leave your details and we will contact you to answer your questions.

    privacy policy

    Solutions that inspire

    All the success stories