MPPT voltage range (25ºC / 35ºC / 50ºC) |
950 V a 1500 V |
MAX MPPT voltage (50ºC) |
1350V |
Min input voltage, min Vdc / Start-up voltage Start-up Vdc |
950V/1100V |
Ambient protection rating |
IP21 (in container IP54) |
Max input voltage, max Vdc |
1500 V |
Max input current Max Idc |
3515 A |
Max short-circuit current |
3400A |
Number of DC inputs |
up to 24 protected by two poles (32 protected by one pole) for photovoltaic inputs |
Max number of DC cables per input |
2 x 800 kcmil, 2 x 400 mm2 |
DC fuse size available (per input) |
200 A, 250 A, 315 A, 350 A, 400 A, 450 A, 500 A |
Nominal AC power with cos phi = 1 (50ºC / 60ºC) |
3300 kVA / 3100 kVA |
Nominal AC power with cos phi = 0.8 (50ºC / 60ºC) |
2640 kW / 2400 kW |
Rated AC current Iac, max = max output current max Iac |
2677 A |
Max distortion coefficient |
<3% at rated power |
AC rated voltage / AC voltage range |
50 Hz / 45 Hz - 55 Hz 60 Hz / 55 Hz - 65 Hz |
AC network frequency / range |
>2 |
Min short-circuit ratio at the AC terminals |
1 / 0.8 inductive to 0.8 capacitive |
Power factor to assigned power / adjustable lag factor |
1 / 0.8 inductive to 0.0 capacitive |
Dimensions (height / width / length) |
2400 / 2200 / 2800 |
Weight |
5250 Kg |
Self-consumption (max. / partial load / average) |
< 8100 W / < 1800 W / < 2000 W |
Self-consumption (on stand-by) |
< 370 W |
Internal auxiliary power supply |
8.5 kVA integrated transformer |
Service temperature range: |
-25 ºC - 60 ºC |
Noise emissions: |
67,8 dB |
Temperature range (on stand-by) |
-40 ºC - 60 ºC |
Temperature range (storage) |
-40 ºC - 70 ºC |
Max relative humidity (with/without condensation) |
95 % to 100 % (2 months/year) / 0 % to 95 % |
Max operating altitude (with/without derating) |
2000 m / 4000 m |
Air consumption |
8000 m3/h |
DC connection |
Cable terminal at each input (without fuse) |
AC connection |
With busbar system (three busbars, one for each phase conductor) |
Communication |
Ethernet, Modbus master, Modbus slave |
ZGR String Monitoring communication |
Modbus TCP / Ethernet (fibre optics, MM, Cat-5) |
Enclosure colour |
Power supply transformer for external equipment |
2.5 kVA integrated transformer |
Compliance with regulations |
EN 61000-6-1, EN 61000-6-2, EN 61000-6-4, EN 61000-3-11, EN 61000-3- 12, EN 62109-1, EN 62109-2, IEC62103, EN 50178, FCC Part 15, AS3100 and UL IEC 62116, UE 2016/631, Arrêté du 9 juin 2020, CEI 0-16, V1:2020-12, Terna A68, G99, VDE-AR-N 4110, P.O.12.2 (NTS), P.O. 12.3, South African Grid Code, Chilean Grid Code, Ecuadorian Grid Code, Peruvian Grid Code, Thailand PEA requirements, IEC61727, UNE 206007-1, ABNT NBR 16149, ABNT NBR 16150, IEEE 1547, IEEE1547.1, GGC&CGC China, DEWA (Dubai) Grid Code, Jordan Grid Code, RETIE Colombia |